Professional chemical pipe manufacturer · Exporter|Factory-direct supply · video factory audit available
Zhejiang Sanli Pipe Technology Co., Ltd.
← Back to knowledge base
Article 07 · Estimating

How many metres of underfloor-heating pipe do you need?

A simple formula using heated area, laying pitch and loop count, so you order the right quantity of PEX/PE-RT coil.

Before you request a quotation for underfloor-heating pipe, a contractor has to settle on one number: total metres. Guessing is expensive in both directions — too much coil ties up cash on the warehouse floor, too little stops the job and forces a costly top-up shipment. The formula and guideline tables below cover the vast majority of standard tenders.

The core formula

N (m) ≈ (heated area in m² ÷ laying pitch in m) × 1.10–1.15 + (number of loops × lead-in distance to the manifold)

The 1.10–1.15 factor is the waste allowance for cutting, wall-edge bends and jump-over loops at doorways. Use 1.15 for awkward room shapes, 1.10 for clean rectangles. The lead-in is the run from the edge of the floor area to the manifold; since supply and return each need a leg, budget roughly double the distance to the manifold per loop.

Laying pitch: metres per m²

The tighter the pitch, the more pipe per square metre. Standard pitches are 100, 150 and 200 mm:

These are estimation guidelines; confirm the exact pitch and metre count against the pipe's specification sheet and the project heat-loss calculation.

Loop length limits

A single loop is limited by hydraulic resistance. As a rule of thumb: for 16×2 mm keep a loop to about 60–80 m, for 20×2 mm about 80–100 m. Bigger zones should be split into several loops rather than stretched into one long circuit.

Which area to count

Run the calculation on the floor area that will actually be piped, not the gross building area on the plan. Deduct:

For a 90 m² flat the real piped area is usually 55–65 m². Getting this step wrong is exactly where the "extra hundred metres" in an order come from, so ask the designer for a layout drawing with the piping boundaries marked before you price the coil.

Worked example: a 90 m² apartment

Floor area to be covered: 60 m² (net of fixed furniture and wet zones). Pitch 150 mm: 60 × 6.7 = 402 m. 12 % waste: 402 × 1.12 ≈ 450 m. Loops: 450 ÷ 75 m ≈ 6 circuits. Lead-ins: 6 × 6 m = 36 m. Total ≈ 486 m → order 500 m.

Rounding up to whole coils

Pipe ships in factory coils of standard length — 100, 120, 200, 240 or 300 m. Always round the final figure up to whole coils: a calculated 486 m becomes five 100 m coils. The tail of one coil is used as the lead-in of the next circuit, so almost nothing is wasted. Never split a loop into joined pieces: a circuit buried in the screed must be one continuous length with no couplings.

Budget the manifold set and the edge-insulation strip separately — they are counted by number of circuits and room perimeter, not by pipe metres. When you request a quotation, also check whether sleeve protection at the manifold is included in the price.

Guideline table: area → metres

Covered area (m²)Pitch 100 mmPitch 150 mmPitch 200 mm
30≈ 330 m≈ 225 m≈ 170 m
50≈ 550 m≈ 375 m≈ 280 m
70≈ 770 m≈ 525 m≈ 395 m
90≈ 990 m≈ 675 m≈ 505 m
120≈ 1 320 m≈ 900 m≈ 675 m

The table already includes a ~10 % allowance and is rounded. Treat it as an example guideline: the real loop layout and lead-in lengths must be verified against your drawings and the supplier's pipe data sheet.

Manifold count & balancing. The number of loops must match the manifold ports — six circuits need a six-way (or 4+2 combined) manifold. Keep loop lengths within about 15 % of each other: otherwise short loops hog the flow, remote rooms stay cold, and balancing the valves becomes a permanent fight. Give rooms with very different loads their own branch instead of one serpentine loop across the whole flat.

Once the metre count is fixed, the next step is logistics — how many of those metres fit in a container and what that does to your landed price. That is the subject of the next articles in this module.

FAQ

Buyer FAQ

How do I estimate how many metres of pipe I need for a project?
Divide the heated floor area by the pipe pitch and add a allowance for the feed runs: metres = area / pitch + waste. For example, 100 m² at a 0.15 m pitch gives about 667 m plus 10-15% for tail and header runs. Use the SANLI knowledge calculator page for a quick estimate.
What is the maximum coil or loop length without joints?
SANLI supplies PEX-AL-PEX and PE-RT pipe in coils up to 100 m with no joints, cutting the number of connections under the floor. The maximum single loop length depends on diameter, typically up to about 100-120 m for 16 mm and shorter for larger sizes. These figures are indicative, so confirm the exact loop length with SANLI for your project.
What temperature and pressure can these pipes handle?
SANLI underfloor-heating pipes are typically rated for a working temperature of about 60-70 °C and short-term peaks up to roughly 90-95 °C. Working pressure depends on the PN class and pipe size, commonly 6-10 bar for heating. Confirm the exact temperature and pressure ratings for your design from the SANLI technical data sheet.
← Back to knowledge base Home

Related guides

Wholesale, OEM private-label and distribution — leave your requirement and get a quote within 24 hours.

Email sanlipipe@163.com · WhatsApp +86 150 6880 2744 · video factory audit available

1-minute enquiry, quote within 24 hours

For wholesale, OEM and distribution. Provide either an email or WhatsApp — required.